Mastering Roof Inspections: Attic Ventilation,
Part 3
by Kenton Shepard and Nick Gromicko
The purpose of the series “Mastering Roof Inspections” is to teach home inspectors,
as well as insurance and roofing professionals, how to recognize proper and improper conditions while inspecting steep-slope,
residential roofs. This series covers roof framing, roofing materials, the attic, and the conditions that affect the roofing
materials and components, including wind and hail.
PASSIVE
SYSTEMS: Part 2
Continuous Ridge
Vent
One of the most efficient ventilation methods
is the continuous soffit vent combined with the continuous ridge vent.
To form the ridge
vent, a slot is cut out of the roof sheathing along the ridge. A fibrous material is installed over the top of the slot and
held in place by a cap. The fibrous material will keep out insects while still allowing air to flow. The cap holds the fiber
in place and diverts air.
Different
manufacturers produce ridge vents in different configurations.
Occasionally, you’ll find a ridge
vent with nothing installed to keep insects out. This is a defective installation.
This grey fabric is one type of barrier,
but you will see other types.
This is the vent for the bathroom exhaust fan improperly terminated
inside the attic. Bathroom and laundry vents should terminate at the outside -- not just beneath the ridge vent…
…and
not under the insulation.
Although thermal buoyancy -- which is the
tendency for hot air to rise -- will evacuate hot air from an attic space or rafter bay, ventilation is much more
effective if the air is actively pulled out of the upper vents by other forces, such as air-pressure differentials.
When ridge vents have baffles, the baffles
divert wind blowing across the roof upward. This creates an area of low pressure just above the opening, producing an
air-pressure differential between the attic space and the exterior, which helps pull air out of the attic.
This effect is lost if the prevailing winds blow parallel to the ridge.
At
the inspection, you may not know the direction from which prevailing winds blow. A home may have a well-designed system which
is poorly oriented to the wind. In this case, it may be out-performed by a more poorly designed system which is better oriented
to the wind.
You don’t have to know exactly how well the ventilation system performs, but
knowing how systems are designed to perform may help if you find a problem that may be related to poor attic or roof ventilation.
You’ll find different types of continuous ridge vents installed. Whatever the type, you should check
to make sure that the cap is securely fastened, since longer nails are required because of the additional thickness.
This ridge vent was improvised using sections
of soffit vent. Obviously, the fasteners did not hold well enough.
Adequate Ventilation
Most home inspection Standards
of Practice require you to comment on the adequacy of attic ventilation.
The most commonly
accepted formula for determining adequate ventilation is a minimum of 12 square inches of net free area for every 150 square
feet of attic space. Twelve square inches might be an opening of 3 inches by 4 inches.
“Net
free” means that louvers or other devices that reduce the actual size of the opening cannot encroach upon the opening.
This minimum can be reduced if a low-perm vapor barrier is installed on the warm side of
the attic floor, which would be beneath the insulation. If this is the case, the formula changes to 12 square inches of net
free area for every 300 square feet of attic space. So, with no air barrier, it’s 150, and with an air barrier, it’s
300.
An example of a commonly installed, low-perm vapor barrier is plastic attached
to the underside of the ceiling joists before the ceiling was drywalled.
RADIANT
BARRIERS
Radiant barriers are materials that are thermally reflective. They reflect heat. They often look like
foil bonded to cardboard. Here’s an example. You may see sheets stapled to roof framing in the attic.
Stapling sheets to the bottoms of rafters will trap hot air in the rafter bays.
Installing them beneath solid roof sheathing
is also unacceptable. This roof originally had wood shakes installed. When they were replaced with asphalt composition shingles,
a radiant barrier was installed on top of the spaced sheathing before a solid roof deck was installed as a substrate for the
shingles.
Heat radiated downward by the roofing materials will be trapped and increase the temperature
on the roof. This condition can contribute to premature failure of roofing materials, especially asphaltic underlayment and
asphalt shingles. It will also void the shingle manufacturer’s warranty. If the radiant barrier installation instructions
conflict with the shingle manufacturer’s instructions, the shingle manufacturer’s instructions should take precedence.
A better installation would be to fasten radiant sheets to the attic floor. The amount of heat radiated to
the living space will be reduced, but the attic ventilation system will still be able to evacuate hot attic air to the outside.
Generally, asphalt shingle manufacturers require that the underside
of the roof sheathing be ventilated for the warranty to be effective.